Used gas engine MWM 800 kW. 2011, operating time – 16,000 engine hours. Cogeneration
Engine Manufacturer MWM (Germany) TCG 2016V08
Power kW 2*400
RPM 1000
Fuel Natural Gas – Methane, Biogas
Generator Marelli, Voltage 400 V, Hz 50
Year of manufacture 2011
Operating hours:
GPD No. 1 – 15,800
GPD No. 2 – 18,750
CHP 8352020 with a capacity of 800 kW with 2 MWM generator sets of 400 kW each.
This is a full-fledged power plant, supplied with panels and auxiliary equipment.
We can arrange professional dismantling and delivery of the equipment.
This plant is in good condition.
The CHP plant is powered by natural gas or biogas.
The thermal energy is in the form of hot water at 90°C and is currently used for district heating.
It has a mixing system for the use of biogas containing 50-65% CH4 coming from the landfill.
The heat recovery system is built next to the generator containers.
The main characteristics of this power plant
Manufactured by the German company MWM.
Commissioned in 2011.
Power generation 2 x 400 kW/400 V/50 Hz
Electrical efficiency 42.8% at the generator poles.
Therman power generation 2 x 395 kW at 90°C
NOx emission level Max. 500 mg/Nm3
Noise level 65 dB(A) at 10 meters.
Engine hours 18750 and 15800 (end of August 2020)
TEAM Evo WMW control system
MWM DSL control PLC
Main equipment:
Gas engines 2 x MWM TCG 2016 V08 C, V8 configuration, 1500 rpm, power 2x400 kW
Generators 2 x Merelli MJB 355 MB4, 400 V/50 Hz, Cos 1.0 board, power 2 x 400 kW.
Gas train, gas mixer, voltage stabilizer, power factor regulator, control unit and switchboard.
Silencer, exhaust heat exchanger, engine cooling systems with plate heat exchangers for pumps and radiators of air ducts of the cooler.
Control cabinets, MMC cabinets, power switches